水暖之家讯:摘 要:对互感器二次回路中两点接地事故的原因进行分析,分析了如何连接各个互感器以避免二次回路中出现两点接地故障,并对设计、安装调试及运行维护中如何规避两点接地事故进行详细阐述。
关键词:互感器;二次回路;两点接地
中图分类号:TK11
Analysis and Prevention of Two-Point Grounding Accident in Secondary Circuit of Instrument Transformer
ZHANG Da-jia
(Shanxi Xishan Thermal Power Co., Ltd., Taiyuan 030022, Shanxi, China)
Abstract: Analyzed the reasons of two-point grounding accident in secondary circuit of instrument transformer, analyzed how to connect various instrument transformers in order to avoid the two-point grounding accidents in secondary circuit, and elaborated how to avoid the two-point grounding accidents in design, installation, commissioning, operation and maintenance in details.
Keywords: instrument transformer; secondary circuit; two-point grounding
0 引言
当前电力运行系统中,继电保护借助电流/电压互感器能显示系统中电力设备所有电流、电压信息,准确提供电力设备在运行中的二次测量值,是确保系统安稳运行的首道防线[1,2]。目前电力运行系统对继电保护多采用微机保护,计算能力强,可用软件对各种复杂保护进行分析。研究继电保护下电压互感器中二次断线的检测方法,对二次单相及多相断线中可能出现的保护误动给予闭锁,避免因为误动导致系统故障,影响电力系统运行。本文主要对电压互感器二次回路中两点接地事故对继电保护影响、原因及防范措施进行详细阐述。
1 两点接地下的误动事故
TA、TV二次回路多分布在室外,连接设备多,分布范围广,在运行过程中因为运行时间长出现绝缘老化,或在一些人为因素下会出现两点接地[3]。 TA、TV二次回路一旦出现了两点接地,保护装置保护动作不正确,会引起大面积停电,威胁电网运行安全。下面对TA、TV二次回路中两点接地事故进行详细分析。
1.1 TA二次回路
2011年9月18日,山西西山热电站220 kV变电站中220 kV母线旁路的201线路内1条线路在断路器运行状态下,1条110 kV出线W出现了接地性故障。这条线路所属断路器对接地故障正确判断,保护性跳闸。与此同时,201断路器对此故障误跳闸,201线路两侧W相断路器出现跳闸,实现重合。
对故障进行检查中发现,此变电站电缆都是年初进行更新的,但对室外一次设备区的端子箱进行拆除检查时发现,线路中仍存在其它接地点。而此次故障的主要原因为:201断路器发出的保护电流通过回路在2号主变压器电缆头位置嵌入到了N相线心,并因此导致201线路中的保护电流回路在室外端子箱处出现了两点接地,而接地点分别位于微机保护下的零序绕组两侧。具体如图1所示,图1中,U、V、W、N分别为201断路器下的并联线路,G点为线路中两点接地点。 Ik为保护回路电流, A。当系统出现接地故障时,故障一次电流会在2个接地点位置之间出现电位差,此电位差会在保护零序绕组内演变成附加电流,使采样电流出现异常,角度出现反相,使零序电流方向保护进入到动作区域,断路器在保护动作下出现保护性跳闸。
图1 TA二次回路的两点接地故障示意图